Q. [R Series] _PARM_SAVE Error After Conversion to TDS
A.
An error may occur in TOP Design Studio (TDS) after conversion due to changes and upgrades in functionality.

We apologize for the inconvenience.
 
The special address [_PARM_SAVE], which was previously used to save recipe data, is no longer supported in TOP Design Studio, and therefore results in a conversion error.
 
 

[Solution]
1. Create a Virtual Address
-. Go to [Project] - [Virtual Address] menu.
-. Click [Add], enter a virtual address name, and set the data type to 'BIT'.
   (In this example, the address name is set to "Parameter Upload".)
 
 
 
2. Configure the Recipe Settings
-. Go to [Project] - [Recipe] menu.
-. In the [Move] page, configure [Parameter Download / Parameter Upload].
   1) Parameter Download(HMI -> PLC): Condition to load recipe data into the PLC.
   2) Parameter Upload(PLC -> HMI): Condition to save PLC data as recipe data.
 
 

3. Replace the _PARM_SAVE Address
-. Change the move condition address for [Parameter Upload] from [_PARM_SAVE] to the newly created virtual address [Parameter Upload].
 
4. Assign Target Item Number
-. Enter the item number in the [Target Item Number] field of Parameter Upload.
-. When the move condition is met, the current PLC data is stored as the recipe data for the specified item (block).
 
 
[Reference]
-. For an example of recipe settings, please refer to post [Examples of Recipe Settings, Parameter Download, and Parameter Upload Features] in the following path on our website: [Service] - [Download] - [Manual/Design] - [Example Files]